Schneider Electric · Harmony XB4 ATEX Series

XB4-BS8445

Active
ATEX IECEX CE

ATEX Emergency Stop Twist Release

Part number: B - S - 844
Schneider Electric Harmony XB4 ATEX Series Introduced circa 2008

ATEX-certified 40mm mushroom emergency stop for hazardous areas.

Common Applications

Critical safety device on oil drilling platforms, gas compressor stations, and chemical reactors. ATEX Zone 1 certification ensures the e-stop itself cannot become an ignition source. Twist-to-release prevents accidental restart in hazardous environments.

Specifications

Actuator Function
Twist-to-release
Actuator Type
Mushroom 40mm
ATEX Zone
Zone 1, Zone 21
Certifications
ATEX, IECEx, CE
Color
Red
Contact Configuration
1NC
Cutout Diameter
22mm
Explosion Group
IIC
IP Rating
IP66
Temperature Class
T6

You'll Also Need

This is a modular component. For a complete assembly, you may also need:

Compatible Alternatives

These products are functionally equivalent cross-references from other manufacturers.

Installation Quick Reference

Panel cutout: 22mm. Mount with the yellow backing plate visible (required by EN/ISO 13850).

Wiring: Wire NC contacts in series with the safety relay input channels. Use dual-channel wiring for SIL 3 / PLe applications. Never wire directly to a motor contactor.

Testing: Press the e-stop and verify the machine stops within the required time. Test the reset mechanism. Repeat monthly per EN/ISO 13850.

Dimensions

Front 22mm cutout 40mm head Side panel terminals

Wiring Diagram

L T 21 22 NC (closed) opens on press

Troubleshooting

E-stop won't reset (twist/pull doesn't release)

Check for debris in the mechanism. For twist-release: turn clockwise 45-90 degrees. For push-pull: pull straight out firmly. If the mechanism is stuck, the internal latch may be damaged — replace the entire head assembly.

Machine doesn't stop when e-stop is pressed

Critical safety issue. Immediately lock out the machine. Check wiring — NC contacts must be in series with the safety relay. Verify the safety relay is functioning. A broken wire in an NC circuit should cause a stop, so check for a wiring bypass.

Safety relay faults after e-stop reset

The safety relay detects a cross-fault between the two monitoring channels. Check that both NC contacts on the e-stop are switching simultaneously. One contact may be welded closed — replace the contact block.