M22-PVL
ActiveATEX Emergency Stop 38mm Push-Pull
Eaton M22 ATEX-certified emergency stop with push-pull reset.
Common Applications
Used on ATEX-certified motor control panels in petrochemical plants and grain handling facilities. Push-pull reset is preferred for cold storage and gloved operations in hazardous atmospheres.
Specifications
|
Actuator Function
Momentary = springs back when released. Maintained/latching = stays pressed until pressed again.
|
Push-pull
|
|
Actuator Type
The button head style. Flush sits level with the bezel (prevents accidental presses). Extended protrudes for easy access.
|
Mushroom 38mm
|
|
ATEX Zone
The hazardous area classification. Zone 1 = gas likely present. Zone 2 = gas unlikely. Zone 21/22 = combustible dust.
|
Zone 1, Zone 21
|
|
Certifications
Third-party safety certifications. UL = required for US NEC installations. CE = EU compliance. CSA = Canadian standards.
|
ATEX, IECEx, CE, UL
|
|
Color
Button/actuator color. Green = start/go, Red = stop/emergency, Yellow = caution, Blue = reset (per IEC 60204-1).
|
Red
|
|
Contact Configuration
Normally Closed — circuit is on until you press. Standard for stop/emergency functions. Wire in series with safety circuits.
|
1NC
|
|
Cutout Diameter
The hole size you drill in your panel to mount this button. 22mm is the most common industrial standard worldwide.
|
22.5mm
|
|
Explosion Group
The gas group the device is certified for. IIC covers hydrogen (most restrictive). IIB covers ethylene. IIA covers propane.
|
IIC
|
|
IP Rating
IP67: Dust-tight and survives temporary water submersion (1m for 30 min). Handles oil splashes, steam cleaning, and rain.
|
IP67
|
|
Temperature Class
Maximum surface temperature. T6 (85°C) is most restrictive. T1 (450°C) is least. Must not exceed auto-ignition temp of the gas.
|
T6
|
Compatible Alternatives
These products are functionally equivalent cross-references from other manufacturers.
Installation Quick Reference
Panel cutout: 22.5mm. Mount with the yellow backing plate visible (required by EN/ISO 13850).
Wiring: Wire NC contacts in series with the safety relay input channels. Use dual-channel wiring for SIL 3 / PLe applications. Never wire directly to a motor contactor.
Testing: Press the e-stop and verify the machine stops within the required time. Test the reset mechanism. Repeat monthly per EN/ISO 13850.
Dimensions
Wiring Diagram
Troubleshooting
E-stop won't reset (twist/pull doesn't release)
Check for debris in the mechanism. For twist-release: turn clockwise 45-90 degrees. For push-pull: pull straight out firmly. If the mechanism is stuck, the internal latch may be damaged — replace the entire head assembly.
Machine doesn't stop when e-stop is pressed
Critical safety issue. Immediately lock out the machine. Check wiring — NC contacts must be in series with the safety relay. Verify the safety relay is functioning. A broken wire in an NC circuit should cause a stop, so check for a wiring bypass.
Safety relay faults after e-stop reset
The safety relay detects a cross-fault between the two monitoring channels. Check that both NC contacts on the e-stop are switching simultaneously. One contact may be welded closed — replace the contact block.
Where to Buy
Price range
$5.32 — $48.61
across 3 distributors
Quick Specs
- Actuator Function
- Push-pull
- Actuator Type
- Mushroom 38mm
- ATEX Zone
- Zone 1, Zone 21
- Certifications
- ATEX, IECEx, CE, UL
- Color
- Red