M22-PVL

Aktivní
ATEX IECEX CE UL

ATEX Emergency Stop 38mm Push-Pull

Katalogové číslo: M22
Eaton M22 ATEX Řada Introduced circa 2010
Eaton M22-PVL — ATEX Emergency Stop 38mm Push-Pull

Eaton M22 ATEX-certified emergency stop with push-pull reset.

Běžné aplikace

Used on ATEX-certified motor control panels in petrochemical plants and grain handling facilities. Push-pull reset is preferred for cold storage and gloved operations in hazardous atmospheres.

Specifikace

Actuator Function
Push-pull
Actuator Type
Mushroom 38mm
ATEX Zone
Zone 1, Zone 21
Certifications
ATEX, IECEx, CE, UL
Color
Red
Contact Configuration
1NC
Cutout Diameter
22.5mm
Explosion Group
IIC
IP Rating
IP67
Temperature Class
T6

Specifikace s touto ikonou odkazují na původní stránku výrobce

Kompatibilní alternativy

Tyto produkty jsou funkčně ekvivalentní křížové reference od jiných výrobců.

Stručný průvodce instalací

Panel cutout: 22.5mm. Mount with the yellow backing plate visible (required by EN/ISO 13850).

Wiring: Wire NC contacts in series with the safety relay input channels. Use dual-channel wiring for SIL 3 / PLe applications. Never wire directly to a motor contactor.

Testing: Press the e-stop and verify the machine stops within the required time. Test the reset mechanism. Repeat monthly per EN/ISO 13850.

Rozměry

Front 22.5mm cutout 40mm head Side panel terminals

Schéma zapojení

L T 21 22 NC (closed) opens on press

Řešení problémů

E-stop won't reset (twist/pull doesn't release)

Check for debris in the mechanism. For twist-release: turn clockwise 45-90 degrees. For push-pull: pull straight out firmly. If the mechanism is stuck, the internal latch may be damaged — replace the entire head assembly.

Machine doesn't stop when e-stop is pressed

Critical safety issue. Immediately lock out the machine. Check wiring — NC contacts must be in series with the safety relay. Verify the safety relay is functioning. A broken wire in an NC circuit should cause a stop, so check for a wiring bypass.

Safety relay faults after e-stop reset

The safety relay detects a cross-fault between the two monitoring channels. Check that both NC contacts on the e-stop are switching simultaneously. One contact may be welded closed — replace the contact block.

Stručné specifikace

Actuator Function
Push-pull
Actuator Type
Mushroom 38mm
ATEX Zone
Zone 1, Zone 21
Certifications
ATEX, IECEx, CE, UL
Color
Red

Co říkají uživatelé

+

“M22-PVL meets EN/ISO 13850 requirements. Always wire NC contacts through a safety relay, never direct to contactor. Test monthly.”

Reddit r/PLC 19 hlasů Zobrazit vlákno →