Schneider Electric · Harmony XALD 시리즈

XALD321

현행 제품
UL CSA CE

Harmony XALD 3-Button Start/Stop/E-Stop Station

Schneider Electric Harmony XALD 시리즈 Introduced circa 2003

Schneider XALD 3-button station — start, stop, and e-stop.

일반적인 용도

Complete motor control station: green start, red stop, and red mushroom e-stop in one IP66 enclosure. The standard for remote motor control on conveyors, pumps, and fans. Meets OSHA requirements for accessible e-stop within reach of the operator.

사양 목록

Certifications
UL, CSA, CE
Color
Green + Red + E-Stop
Contact Configuration
2x 1NO + 1NC (e-stop)
IP Rating
IP66
Mounting Type
Surface mount (enclosed)

설치 빠른 참조

Panel cutout: 22mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).

Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.

Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.

외형 치수

배선도

11 12 NO 21 22 NC

문제 해결

Button doesn't respond when pressed

Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.

Works intermittently

Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.

Button feels mushy or doesn't click

The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.

구매처

가격 범위

$5.37 — $45.32

2개 대리점

주요 사양

Certifications
UL, CSA, CE
Color
Green + Red + E-Stop
Contact Configuration
2x 1NO + 1NC (e-stop)
IP Rating
IP66
Mounting Type
Surface mount (enclosed)

사용자 후기

+

“Complete motor control station: green start, red stop, and red mushroom e-stop in one IP66 enclosure. The standard for remote motor control on conveyors, pumps, and fans. Meets OSHA requirements for a”

Reddit r/PLC 12 추천 스레드 보기 →