Eaton · M22 Seria

M22-D-Y

Aktywny
UL CSA CE ATEX

M22 Yellow Flush Push Button

Numer katalogowy: M22 - D - Y
Eaton M22 Seria Introduced circa 2000
Eaton M22-D-Y — M22 Yellow Flush Push Button

Yellow flush momentary push button for Eaton M22 series. 22.5mm cutout, IP67 front. Complete unit with 1NO contact.

Typowe Zastosowania

Yellow push button used for abnormal or intervention functions per IEC 60204-1 — yellow signals caution or an action to suppress an abnormal condition. Common on conveyor systems for jam-clear functions, packaging lines for fault reset, and process control panels for alarm acknowledgement. In many panel designs, the yellow button sits between the green start and red stop as the operator's go-to for clearing faults without a full restart. The M22 series IP67 front face handles washdown environments. Pairs with the M22-D-G (green start) and M22-D-R (red stop) for a complete three-button station.

Specyfikacje

Actuator Shape
Round
Actuator Type
Flush
Certifications
UL, CSA, CE, ATEX
Color
Yellow
Contact Configuration
1NO
Cutout Diameter
22.5mm
IP Rating
IP67 (front)
Material
Plastic/Metal bezel
Mechanical Life
5,000,000 cycles
Mounting Type
Panel
Max Operating Temp
70°C
Min Operating Temp
-25°C

Specyfikacje z tą ikoną są powiązane z oryginalną stroną źródłową producenta

Będziesz Potrzebować Również

To jest komponent modułowy. Do kompletnego zestawu mogą być potrzebne również:

Kompatybilne Alternatywy

Te produkty to funkcjonalnie równoważne odnośniki krzyżowe od innych producentów.

Skrócona Instrukcja Montażu

Panel cutout: 22.5mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).

Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.

Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.

Wymiary

Front 22.5mm cutout panel hole diameter Side panel contact ~45mm depth

Schemat Połączeń

L T 11 12 NO (open) press ↓

Rozwiązywanie Problemów

Button doesn't respond when pressed

Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.

Works intermittently

Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.

Button feels mushy or doesn't click

The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.

Skrócone Specyfikacje

Actuator Shape
Round
Actuator Type
Flush
Certifications
UL, CSA, CE, ATEX
Color
Yellow
Contact Configuration
1NO

Co Mówią Użytkownicy

“Yellow means caution or intervention per IEC 60204-1. We use them for reset buttons after a fault, jog functions, and test/manual override. Never use yellow for start or stop — that confuses operators.”

Reddit r/PLC by standards_nerd 27 głosy za Zobacz wątek →

Źródła Danych

Specyfikacje i dane produktowe pochodzą z poniższych źródeł.

Eaton M22-D-Y Product Page

https://www.eaton.com/us/en-us/skuPage.M22-D-Y.html

Data dostępu: March 29, 2026

Źródło