GDL31-GP
現行品ATEX Green Push Button GRP Enclosure
Pepperl+Fuchs ATEX-certified green push button in GRP (fiberglass) enclosure for Zone 1.
主な用途
Purpose-built for hazardous area installations where the entire button assembly must be explosion-proof. The GRP (glass-reinforced polyester) enclosure is corrosion-resistant and lighter than cast aluminum — preferred on offshore oil platforms where weight and salt spray are concerns.
仕様一覧
|
ATEX Zone
The hazardous area classification. Zone 1 = gas likely present. Zone 2 = gas unlikely. Zone 21/22 = combustible dust.
|
Zone 1, Zone 2
|
|
Certifications
Third-party safety certifications. UL = required for US NEC installations. CE = EU compliance. CSA = Canadian standards.
|
ATEX, IECEx
|
|
Color
Button/actuator color. Green = start/go, Red = stop/emergency, Yellow = caution, Blue = reset (per IEC 60204-1).
|
Green
|
|
Contact Configuration
Normally Open — circuit is off until you press. Standard for start/go/enable functions.
|
1NO
|
|
Cutout Diameter
The hole size you drill in your panel to mount this button. 22mm is the most common industrial standard worldwide.
|
22mm
|
|
Explosion Group
The gas group the device is certified for. IIC covers hydrogen (most restrictive). IIB covers ethylene. IIA covers propane.
|
IIC
|
|
IP Rating
IP66: Dust-tight and withstands powerful water jets from any direction. Standard for outdoor and washdown applications.
|
IP66
|
|
Material
The bezel/body material. Metal bezels are more durable in harsh environments. Plastic is lighter and cheaper.
|
GRP (fiberglass)
|
|
Temperature Class
Maximum surface temperature. T6 (85°C) is most restrictive. T1 (450°C) is least. Must not exceed auto-ignition temp of the gas.
|
T6
|
このアイコン付きの仕様は、メーカーの元ソースページにリンクしています
取付クイックリファレンス
Panel cutout: 22mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).
Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.
Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.
外形寸法
配線図
トラブルシューティング
Button doesn't respond when pressed
Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.
Works intermittently
Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.
Button feels mushy or doesn't click
The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.
購入先
価格帯
$9.97 — $57.87
3 社の販売代理店
主要仕様
- ATEX Zone
- Zone 1, Zone 2
- Certifications
- ATEX, IECEx
- Color
- Green
- Contact Configuration
- 1NO
- Cutout Diameter
- 22mm
ユーザーの声
“Make sure you get Zone 1 rated, not just Zone 2. The Schneider XB4 ATEX range is solid but the Pepperl+Fuchs units with GRP enclosures are better for offshore where salt spray is a factor.”
詳しく見る
データソース
仕様および製品データは以下の参考資料に基づいています。
GDL31-GP Product Page
https://www.pepperl-fuchs.com/global/en/search.htm?q=GDL31