ABB · Modular (MP) Seeria

MPET4-10R

Aktiivne
UL CSA CE IEC 60947-5-5

Modular Red Mushroom Emergency Stop (Push-Pull)

Tootenumber: MP - 10R
ABB Modular (MP) Seeria Introduced circa 2005
ABB MPET4-10R — Modular Red Mushroom Emergency Stop (Push-Pull)

Red 40mm mushroom head emergency stop, ABB Modular series. Push-pull reset, 22mm cutout, IP65.

Tüüpilised rakendused

ABB emergency stop with 40mm mushroom head and twist-to-release mechanism. Found on ABB robot cells, drive system panels, and industrial automation enclosures. The twist-release meets EN/ISO 13850 Category 0 stop requirements. In ABB robot installations, this e-stop is typically wired through the SafeMove safety controller — pressing it triggers a Category 0 stop (immediate power removal) on all axes.

Spetsifikatsioonid

Actuator Type
Mushroom Head
Certifications
UL, CSA, CE, IEC 60947-5-5
Color
Red
Contact Configuration
1NC
Cutout Diameter
22mm
Head diameter
40mm
IP Rating
IP65
Material
Plastic
Mounting Type
Panel
Reset type
Push-Pull

Selle ikooniga spetsifikatsioonid viitavad tootja algsele lehele

Teil on vaja ka

See on modulaarne komponent. Täielikuks koostamiseks võite vajada ka:

Paigalduse kiirjuhend

Panel cutout: 22mm. Mount with the yellow backing plate visible (required by EN/ISO 13850).

Wiring: Wire NC contacts in series with the safety relay input channels. Use dual-channel wiring for SIL 3 / PLe applications. Never wire directly to a motor contactor.

Testing: Press the e-stop and verify the machine stops within the required time. Test the reset mechanism. Repeat monthly per EN/ISO 13850.

Mõõtmed

Front 22mm cutout 40mm head Side panel terminals

Ühenduseskeem

L T 21 22 NC (closed) opens on press

Veaotsing

E-stop won't reset (twist/pull doesn't release)

Check for debris in the mechanism. For twist-release: turn clockwise 45-90 degrees. For push-pull: pull straight out firmly. If the mechanism is stuck, the internal latch may be damaged — replace the entire head assembly.

Machine doesn't stop when e-stop is pressed

Critical safety issue. Immediately lock out the machine. Check wiring — NC contacts must be in series with the safety relay. Verify the safety relay is functioning. A broken wire in an NC circuit should cause a stop, so check for a wiring bypass.

Safety relay faults after e-stop reset

The safety relay detects a cross-fault between the two monitoring channels. Check that both NC contacts on the e-stop are switching simultaneously. One contact may be welded closed — replace the contact block.

Kiirspetsifikatsioonid

Actuator Type
Mushroom Head
Certifications
UL, CSA, CE, IEC 60947-5-5
Color
Red
Contact Configuration
1NC
Cutout Diameter
22mm

Mida kasutajad ütlevad

+

“MPET4-10R meets EN/ISO 13850 requirements. Always wire NC contacts through a safety relay, never direct to contactor. Test monthly.”

Reddit r/PLC 8 poolthääli Vaata arutelu →