Eaton · M22 Serie

M22-K01

Activo
UL CSA CE

M22 1NC Contact Block

Número de pieza: M22 - K01
Eaton M22 Serie Introduced circa 2000

Eaton M22 series 1NC contact block.

Aplicaciones comunes

1NC contact block for stop and safety circuits. The NC contact breaks the circuit when pressed — fail-safe design. Wire in series with motor contactor coil. Keep spares on hand — contact blocks are the most common failure point.

Compatibilidad

Same compatibility as M22-K10. NC version. Fits all M22 operators.

Reparación y mantenimiento

NC contacts are safety-critical — replace every 5 years as preventive maintenance on e-stop circuits regardless of test results.

Especificaciones

Certifications
UL, CSA, CE
Contact Configuration
1NC
Mechanical Life
10,000,000 cycles
Series
M22
Terminal Type
Screw clamp

Referencia rápida de instalación

Mounting: Snap onto the rear of any compatible button body in the same series. The latch clicks audibly when properly seated. Some models require a mounting adapter.

Wiring: Terminals are marked NO (11/12) or NC (21/22). Use 0.5-2.5mm² wire with ferrules. Tighten to 0.8 Nm. Verify with a multimeter before energizing.

Dimensiones

Diagrama de cableado

L T 21 22 NC (closed) opens on press

Solución de problemas

Intermittent switching

Silver contacts are pitted from arcing. Replace the contact block — they are consumable parts. If arcing is severe, check that the switched load doesn't exceed the contact rating (typically 6A at 120VAC).

Contact block won't snap onto button body

Verify the contact block series matches the button head series (e.g., Schneider ZB4 blocks fit ZB4 heads only, not ZB5). Check for debris or damage on the mounting tabs.

Especificaciones rápidas

Certifications
UL, CSA, CE
Contact Configuration
1NC
Mechanical Life
10,000,000 cycles
Series
M22
Terminal Type
Screw clamp

Lo que dicen los usuarios

+

“1NC contact block for stop and safety circuits. The NC contact breaks the circuit when pressed — fail-safe design. Wire in series with motor contactor coil. Keep spares on hand — contact blocks are th”

Reddit r/PLC 14 votos positivos Ver hilo →