ABB · MP Řada

MP3-10Y

Aktivní
UL CSA CE

22mm Yellow Extended Pushbutton Head (ABB Modular)

Katalogové číslo: MP - 3
ABB MP Řada Introduced circa 2005

ABB modular yellow extended push button.

Běžné aplikace

Extended yellow for intervention/caution on ABB panels.

Specifikace

Actuator Type
Extended
Bezel
Black plastic
Certifications
UL, CSA, CE
Color
Yellow
Component type
Head/operator only (contact block + MCBH holder separate)
Contact Configuration
None integral — add MCB-10 (1NO)/MCB-01 (1NC) via MCBH holder
Cutout Diameter
22mm
IP Rating
IP66 (front) / IP20 (terminals); NEMA 1/3R/4/4X/12/13
Operating temp
-25 to +70 C

Stručný průvodce instalací

Panel cutout: 22mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).

Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.

Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.

Rozměry

Front 22mm cutout panel hole diameter Side panel contact ~45mm depth

Schéma zapojení

11 12 NO 21 22 NC

Řešení problémů

Button doesn't respond when pressed

Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.

Works intermittently

Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.

Button feels mushy or doesn't click

The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.

Stručné specifikace

Actuator Type
Extended
Bezel
Black plastic
Certifications
UL, CSA, CE
Color
Yellow
Component type
Head/operator only (contact block + MCBH holder separate)

Co říkají uživatelé

+

“Extended yellow for intervention/caution on ABB panels.”