3SU1801-0AB00-2AB1
AttivoSiemens SIRIUS ACT 3SU1 1-Button Green I Control Station (3SU1801-0AB00-2AB1)
Siemens SIRIUS ACT enclosed 2-button start/stop station.
Applicazioni Comuni
Green start + red stop in an IP67 enclosure. Metal front ring buttons inside. TIA Portal configurable when connected via AS-Interface. The premium enclosed station for Siemens-controlled plants.
Specifiche
|
Certifications
Third-party safety certifications. UL = required for US NEC installations. CE = EU compliance. CSA = Canadian standards.
|
UL, CSA, CE
|
|
Color
Button/actuator color. Green = start/go, Red = stop/emergency, Yellow = caution, Blue = reset (per IEC 60204-1).
|
Green (single I button)
|
|
Contact Configuration
Normally Closed — circuit is on until you press. Standard for stop/emergency functions. Wire in series with safety circuits.
|
1NC
|
|
IP Rating
IP69K: Dust-tight and withstands high-pressure, high-temperature steam jets. Built for food processing washdown environments.
|
IP66 / IP67 / IP69
|
|
Mounting Type
How the button attaches to the panel. Panel mount is standard — installs through a cutout from the front.
|
Surface mount (enclosed)
|
|
Operators
|
1x green pushbutton, I (start/on) label
|
|
Pn note
|
Corrected: 3SU1801-0AB00-2AB1 = SINGLE green I pushbutton station, 1NC (Siemens/RS). Was mislabeled 2-button green/red start/stop with 1NO+1NC.
|
|
Pn status
|
mislabel-corrected
|
|
Series
The manufacturer's product family. Products in the same series share mounting systems and accessories.
|
Siemens SIRIUS ACT 3SU1 (current 22mm)
|
Guida Rapida all'Installazione
Panel cutout: 22mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).
Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.
Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.
Dimensioni
Schema di Cablaggio
Risoluzione dei Problemi
Button doesn't respond when pressed
Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.
Works intermittently
Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.
Button feels mushy or doesn't click
The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.
Dove Acquistare
Fascia di prezzo
$84.76 — $126.74
presso 3 distributori
Specifiche Rapide
- Certifications
- UL, CSA, CE
- Color
- Green (single I button)
- Contact Configuration
- 1NC
- IP Rating
- IP66 / IP67 / IP69
- Mounting Type
- Surface mount (enclosed)
Cosa Dicono gli Utenti
“Green start + red stop in an IP67 enclosure. Metal front ring buttons inside. TIA Portal configurable when connected via AS-Interface. The premium enclosed station for Siemens-controlled plants.”
Approfondisci
Classificazioni IP Spiegate
Cosa significano IP65, IP66, IP67, IP69K per la Sua applicazione
Guida 22mm vs 30mm
Quale dimensione del foro pannello Le serve?
Blocchi Contatti: NO vs NC
Come scegliere e cablare i blocchi contatti
Strumento Trova Pulsante