Guida Rapida all'Installazione

Panel cutout: 22mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).

Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.

Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.

Dimensioni

Front 22mm cutout panel hole diameter Side panel contact ~45mm depth

Schema di Cablaggio

L T 21 22 NC (closed) opens on press

Risoluzione dei Problemi

Button doesn't respond when pressed

Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.

Works intermittently

Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.

Button feels mushy or doesn't click

The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.

Dove Acquistare

Fascia di prezzo

$19.46 — $30.95

presso 2 distributori

Specifiche Rapide

Certifications
UL, CSA, CE
Color
Red
Contact Configuration
1NC
Cutout Diameter
22mm
Illumination
Illuminated

Cosa Dicono gli Utenti

+

“Illuminated red for fault acknowledgement on AB panels. LED lit = fault active. Press to acknowledge. Replaces the need for a separate stop button and fault indicator.”

Reddit r/PLC 33 voti positivi Vedi discussione →