A22-01
ActivoA22 1NC Contact Block
Omron A22 1NC contact block.
Aplicaciones comunes
NC contact block for Omron A22 stop buttons and safety circuits.
Especificaciones
|
Certifications
Third-party safety certifications. UL = required for US NEC installations. CE = EU compliance. CSA = Canadian standards.
|
UL, CE
|
|
Contact Configuration
Normally Closed — circuit is on until you press. Standard for stop/emergency functions. Wire in series with safety circuits.
|
1NC
|
|
Mechanical Life
How many press cycles before mechanical failure. Higher is better — 10M cycles at 100 presses/day = 274 years.
|
10,000,000 cycles
|
|
Terminal Type
How you connect wires. Screw clamp is most common in industrial. Spring cage is faster but requires proper ferrules.
|
Screw clamp
|
Referencia rápida de instalación
Mounting: Snap onto the rear of any compatible button body in the same series. The latch clicks audibly when properly seated. Some models require a mounting adapter.
Wiring: Terminals are marked NO (11/12) or NC (21/22). Use 0.5-2.5mm² wire with ferrules. Tighten to 0.8 Nm. Verify with a multimeter before energizing.
Dimensiones
Diagrama de cableado
Solución de problemas
Intermittent switching
Silver contacts are pitted from arcing. Replace the contact block — they are consumable parts. If arcing is severe, check that the switched load doesn't exceed the contact rating (typically 6A at 120VAC).
Contact block won't snap onto button body
Verify the contact block series matches the button head series (e.g., Schneider ZB4 blocks fit ZB4 heads only, not ZB5). Check for debris or damage on the mounting tabs.
Dónde comprar
Rango de precios
$13.15 — $58.29
en 3 distribuidores
Especificaciones rápidas
- Certifications
- UL, CE
- Contact Configuration
- 1NC
- Mechanical Life
- 10,000,000 cycles
- Terminal Type
- Screw clamp
Lo que dicen los usuarios
“NC contact block for Omron A22 stop buttons and safety circuits.”