Siemens · SIRIUS ACT Baureihe

3SU1132-0AB20-1BA1

Aktiv
UL CSA CE

SIRIUS ACT Red Illuminated Flush 24V

Artikelnummer: 3SU1 - 1 - 20
Siemens SIRIUS ACT Baureihe Introduced circa 2013

Siemens SIRIUS ACT illuminated red flush button.

Typische Anwendungen

Red illuminated for fault/stop on Siemens panels. LED lit = fault active. Metal front ring.

Spezifikationen

Certifications
UL, CSA, CE
Color
Red
Contact Configuration
1NC
Cutout Diameter
22mm
Illumination
Illuminated
IP Rating
IP67
LED Voltage
24V AC/DC
Material
Metal front ring

Installationskurzanleitung

Panel cutout: 22mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).

Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.

Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.

Abmessungen

Front 22mm cutout panel hole diameter Side panel contact ~45mm depth

Schaltplan

L T 21 22 NC (closed) opens on press

Fehlerbehebung

Button doesn't respond when pressed

Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.

Works intermittently

Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.

Button feels mushy or doesn't click

The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.

Bezugsquellen

Preisbereich

$65.12 — $66.98

bei 2 Händlern

Kurzspezifikationen

Certifications
UL, CSA, CE
Color
Red
Contact Configuration
1NC
Cutout Diameter
22mm
Illumination
Illuminated

Das sagen Anwender

+

“Red illuminated for fault/stop on Siemens panels. LED lit = fault active. Metal front ring.”

Reddit r/PLC 40 Bewertungen Thread anzeigen →