IDEC · HW Řada

HW-C01

Aktivní
UL CE

HW 1NC Contact Block

IDEC HW Řada Introduced circa 2005

IDEC HW series 1NC contact block.

Běžné aplikace

NC contact block for stop functions. Same IDEC value pricing. Keep spares — contact blocks are consumables.

Specifikace

Certifications
UL, CE
Contact Configuration
1NC
Mechanical Life
10,000,000 cycles
Terminal Type
Screw clamp

Stručný průvodce instalací

Mounting: Snap onto the rear of any compatible button body in the same series. The latch clicks audibly when properly seated. Some models require a mounting adapter.

Wiring: Terminals are marked NO (11/12) or NC (21/22). Use 0.5-2.5mm² wire with ferrules. Tighten to 0.8 Nm. Verify with a multimeter before energizing.

Rozměry

Schéma zapojení

L T 21 22 NC (closed) opens on press

Řešení problémů

Intermittent switching

Silver contacts are pitted from arcing. Replace the contact block — they are consumable parts. If arcing is severe, check that the switched load doesn't exceed the contact rating (typically 6A at 120VAC).

Contact block won't snap onto button body

Verify the contact block series matches the button head series (e.g., Schneider ZB4 blocks fit ZB4 heads only, not ZB5). Check for debris or damage on the mounting tabs.

Stručné specifikace

Certifications
UL, CE
Contact Configuration
1NC
Mechanical Life
10,000,000 cycles
Terminal Type
Screw clamp

Co říkají uživatelé

+

“NC contact block for stop functions. Same IDEC value pricing. Keep spares — contact blocks are consumables.”

Reddit r/PLC 20 hlasů Zobrazit vlákno →