M22-DDL-GR-K7

Hoạt động
UL CSA CE

M22 Green/Red Double Illuminated Button

Mã sản phẩm: M22
Eaton M22 Dòng sản phẩm Introduced circa 2008

Eaton M22 double-actuator green/red illuminated button — start and stop in one unit.

Ứng Dụng Phổ Biến

Start/stop in a single device — green button on top, red on bottom, both illuminated. Saves panel space. Green lit = running. Red lit = stopped/fault. Common on compact control stations where panel real estate is limited.

Thông số kỹ thuật

Certifications
UL, CSA, CE
Color
Green/Red dual
Contact Configuration
1NO + 1NC
Cutout Diameter
22.5mm
Illumination
Dual LED
IP Rating
IP67 (front)
LED Voltage
24V AC/DC
Series
M22

Hướng Dẫn Cài Đặt Nhanh

Panel cutout: 22.5mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).

Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.

Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.

Kích thước

Front 22.5mm cutout panel hole diameter Side panel contact ~45mm depth

Sơ đồ đấu dây

11 12 NO 21 22 NC

Khắc phục sự cố

Button doesn't respond when pressed

Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.

Works intermittently

Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.

Button feels mushy or doesn't click

The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.

Nơi Mua Hàng

Dải giá

$5.92 — $6.08

từ 2 nhà phân phối

Thông số kỹ thuật nhanh

Certifications
UL, CSA, CE
Color
Green/Red dual
Contact Configuration
1NO + 1NC
Cutout Diameter
22.5mm
Illumination
Dual LED

Những Đánh Giá Từ Khách Hàng

“Start/stop in a single device — green button on top, red on bottom, both illuminated. Saves panel space. Green lit = running. Red lit = stopped/fault. Common on compact control stations where panel re”

Reddit r/PLC 23 lượt bình chọn Xem ren