Allen-Bradley · 800F Dòng sản phẩm

800F-LY4

Hoạt động
UL CSA CE

22mm Yellow Illuminated Push Button 24V

Allen-Bradley 800F Dòng sản phẩm Introduced circa 2005

Allen-Bradley 800F illuminated yellow push button.

Ứng Dụng Phổ Biến

Illuminated yellow for caution/intervention on AB panels. LED lit = function active. Press for jog, test mode, or manual override. The yellow illumination provides both color-coding and status indication in one button.

Thông số kỹ thuật

Certifications
UL, CSA, CE
Color
Yellow
Contact Configuration
1NO
Cutout Diameter
22mm
Illumination
Illuminated
IP Rating
IP66
LED Voltage
24V AC/DC

Hướng Dẫn Cài Đặt Nhanh

Panel cutout: 22mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).

Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.

Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.

Kích thước

Front 22mm cutout panel hole diameter Side panel contact ~45mm depth

Sơ đồ đấu dây

L T 11 12 NO (open) press ↓

Khắc phục sự cố

Button doesn't respond when pressed

Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.

Works intermittently

Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.

Button feels mushy or doesn't click

The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.

Nơi Mua Hàng

Dải giá

$31.52 — $49.84

từ 2 nhà phân phối

Thông số kỹ thuật nhanh

Certifications
UL, CSA, CE
Color
Yellow
Contact Configuration
1NO
Cutout Diameter
22mm
Illumination
Illuminated

Những Đánh Giá Từ Khách Hàng

“Illuminated yellow for caution/intervention on AB panels. LED lit = function active. Press for jog, test mode, or manual override. The yellow illumination provides both color-coding and status indicat”

Reddit r/PLC 28 lượt bình chọn Xem ren