Allen-Bradley · 800F Series

800F-A4A2

Active
UL CSA CE

22mm Red Flush Push Button 1NC

Allen-Bradley 800F Series Introduced circa 2005

Allen-Bradley 800F series red flush momentary push button with 1NC contact block.

Common Applications

Standard stop button on Allen-Bradley panels. Pairs with 800F-A3A1 green start. Red color and 1NC contact follow NFPA 79.

Specifications

Actuator Function
Momentary
Actuator Type
Flush
Certifications
UL, CSA, CE
Color
Red
Contact Configuration
1NC
Cutout Diameter
22mm
IP Rating
IP66
Material
Plastic with chrome bezel
Mounting Type
Panel

Installation Quick Reference

Panel cutout: 22mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).

Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.

Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.

Dimensions

Front 22mm cutout panel hole diameter Side panel contact ~45mm depth

Wiring Diagram

L T 21 22 NC (closed) opens on press

Troubleshooting

Button doesn't respond when pressed

Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.

Works intermittently

Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.

Button feels mushy or doesn't click

The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.

Where to Buy

Price range

$23.78 — $40.36

across 2 distributors

Quick Specs

Actuator Function
Momentary
Actuator Type
Flush
Certifications
UL, CSA, CE
Color
Red
Contact Configuration
1NC

What People Are Saying

+

“Hundreds of these across our plants. Not a single failure in 10 years that wasnt caused by physical damage. The integrated contact block means fewer parts to assemble.”

Reddit r/PLC by maintenance_mgr 22 upvotes View thread →