Eaton · M22 Serie

M22-DL-Y

Attivo
UL CSA CE

22mm Yellow Illuminated Flush Button 24V

Codice articolo: M22 - DL - Y
Eaton M22 Serie Introduced circa 2000

Eaton M22 illuminated yellow flush push button.

Applicazioni Comuni

Yellow illuminated for caution functions on Eaton panels. LED indicates active status. Used for manual override, test mode, and jog functions.

Specifiche

Certifications
UL, CSA, CE
Color
Yellow
Contact Configuration
1NO
Cutout Diameter
22.5mm
Illumination
Illuminated
IP Rating
IP67 (front)
LED Voltage
24V AC/DC
Series
M22

Guida Rapida all'Installazione

Panel cutout: 22.5mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).

Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.

Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.

Dimensioni

Front 22.5mm cutout panel hole diameter Side panel contact ~45mm depth

Schema di Cablaggio

L T 11 12 NO (open) press ↓

Risoluzione dei Problemi

Button doesn't respond when pressed

Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.

Works intermittently

Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.

Button feels mushy or doesn't click

The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.

Specifiche Rapide

Certifications
UL, CSA, CE
Color
Yellow
Contact Configuration
1NO
Cutout Diameter
22.5mm
Illumination
Illuminated