Schneider Electric · Harmony XB4 Baureihe

ZB4-BP2

Aktiv
UL CSA CE

Schneider ZB4BP2 Black Projecting Pushbutton Head (Harmony XB4)

Artikelnummer: ZB4 - B
Schneider Electric Harmony XB4 Baureihe Introduced circa 2003

Schneider XB4 red guarded (shrouded) push button.

Typische Anwendungen

Guarded button with a raised ring around the actuator that prevents accidental presses. Used for stop buttons near moving machinery where operators might lean against the panel. The guard forces deliberate pressing — you have to reach over the ring to press the button. Also used for critical functions where accidental activation would be costly.

Spezifikationen

Actuator Function
Momentary
Actuator Type
Projecting (raised, ~Ø29.5mm cap)
Certifications
UL, CSA, CE
Color
Black
Contact Configuration
None integral (head-only; add ZB4 contact block)
Cutout Diameter
22mm
Device type
ZB4 HEAD only (non-illuminated black projecting, momentary); complete unit = XB4-BP2
IP Rating
IP66
Material
Metal
Pn note
Corrected: ZB4BP2 = BLACK PROJECTING pushbutton head (se.com datasheet: black projecting Ø22 spring return), not red/guarded. Color 2=black; BP=projecting actuator.

Installationskurzanleitung

Panel cutout: 22mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).

Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.

Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.

Abmessungen

Front 22mm cutout panel hole diameter Side panel contact ~45mm depth

Schaltplan

L T 11 12 NO (open) press ↓

Fehlerbehebung

Button doesn't respond when pressed

Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.

Works intermittently

Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.

Button feels mushy or doesn't click

The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.

Kurzspezifikationen

Actuator Function
Momentary
Actuator Type
Projecting (raised, ~Ø29.5mm cap)
Certifications
UL, CSA, CE
Color
Black
Contact Configuration
None integral (head-only; add ZB4 contact block)