SICK · i10 Series

6045755

Active
CE UL SIL 3 PLE

i10-E0233 Lock Safety Command Device

SICK i10 Series Introduced circa 2020

SICK i10 safety command device — e-stop with integrated RFID guard monitoring.

Common Applications

Next-generation safety station combining RFID-coded guard monitoring with e-stop. The RFID sensor detects the specific guard door — prevents bypassing with magnets. Found on collaborative robot cells and high-risk packaging lines. Wire to SICK Flexi safety controller.

Specifications

Actuator Function
Twist-release
Actuator Type
Mushroom 40mm
Certifications
CE, UL, SIL 3, PLe
Contact Configuration
2 OSSD + e-stop
IP Rating
IP67
Protocol
OSSD (solid-state safety output)

Installation Quick Reference

Panel cutout: 22mm. Mount with the yellow backing plate visible (required by EN/ISO 13850).

Wiring: Wire NC contacts in series with the safety relay input channels. Use dual-channel wiring for SIL 3 / PLe applications. Never wire directly to a motor contactor.

Testing: Press the e-stop and verify the machine stops within the required time. Test the reset mechanism. Repeat monthly per EN/ISO 13850.

Dimensions

Wiring Diagram

Troubleshooting

E-stop won't reset (twist/pull doesn't release)

Check for debris in the mechanism. For twist-release: turn clockwise 45-90 degrees. For push-pull: pull straight out firmly. If the mechanism is stuck, the internal latch may be damaged — replace the entire head assembly.

Machine doesn't stop when e-stop is pressed

Critical safety issue. Immediately lock out the machine. Check wiring — NC contacts must be in series with the safety relay. Verify the safety relay is functioning. A broken wire in an NC circuit should cause a stop, so check for a wiring bypass.

Safety relay faults after e-stop reset

The safety relay detects a cross-fault between the two monitoring channels. Check that both NC contacts on the e-stop are switching simultaneously. One contact may be welded closed — replace the contact block.

Where to Buy

Price range

$2.34 — $22.68

across 2 distributors

Quick Specs

Actuator Function
Twist-release
Actuator Type
Mushroom 40mm
Certifications
CE, UL, SIL 3, PLe
Contact Configuration
2 OSSD + e-stop
IP Rating
IP67

What People Are Saying

+

“Next-generation safety station combining RFID-coded guard monitoring with e-stop. The RFID sensor detects the specific guard door — prevents bypassing with magnets. Found on collaborative robot cells ”

Reddit r/PLC 10 upvotes View thread →