Switch Fixings PUSH BUTTON ENCL 600VAC 10A XALB SP
Research Notes
1. What this is
XALD01H7 is a Schneider Electric Harmony XALD enclosed plastic control station (pre-wired pushbutton/E-stop station).
2. Part-number decode
- Series: Harmony XALD
- Panel cutout: 22mm
- Bezel material: Plastic
- Type: control station
3. Compatibility & ordering
Schneider's Harmony (22/16mm) and Square D Class 9001 (30mm) are the reference IEC/US command-switch ranges. Match by size (16/22/30mm), bezel material (metal XB4/ZB4 vs plastic XB5/ZB5), function (pushbutton/selector/indicator/E-stop), colour, illumination, and contact arrangement; cross-reference to Allen-Bradley 800F/800T, Siemens 3SU, IDEC HW, or Eaton M22 by the same attributes if needed.
4. Data-quality note
The Schneider series, bezel material, size, and component type are decoded from the part number (grounded in the se.com Harmony catalog and distributor listings). The exact colour and contact arrangement are encoded in the remaining digits and depend on the sub-family — confirm against the Schneider datasheet for a precise order (not guessed here).
5. Sources
- Schneider Electric Harmony / Square D Class 9001 catalog (se.com)
- Distributor listing (Rexel / Mouser / Newark) — search the exact part number
1 source
- Schneider Electric — XALD01H7 — se.com
Specifications
|
Bezel material
|
plastic
|
|
Component type
|
control station
|
|
Enriched by
|
schneider-decoder-2026-08-12
|
|
Lead time
|
30 Days
|
|
Manufacturer series
|
Harmony XALD
|
|
Mouser part number
|
996-XALD01H7
|
|
Panel cutout
|
22mm
|
|
Pn status
|
decoded
|
|
Wireless Range
Maximum wireless range in open air. Walls and interference reduce this significantly.
|
Harmony / Square D Class 9001
|
|
Rohs status
|
|
|
Series description
|
Schneider Harmony XALD enclosed plastic control station (pre-wired pushbutton/E-stop station)
|
Installation Quick Reference
Panel cutout: 22mm. Insert from the front of the panel, secure with mounting nut from behind (tighten to 2-3 Nm).
Contact block: Snap or screw the contact block onto the rear of the button body. Ensure the contact block orientation matches the wiring diagram — NO terminals are usually marked.
Wiring: Use 0.5-2.5mm² stranded wire with ferrules. Tighten screw terminals to 0.8 Nm. Test the button function before energizing the circuit.
Dimensions
Troubleshooting
Button doesn't respond when pressed
Check the contact block first — it's the most common failure point. Test continuity across the NO or NC terminals with a multimeter. If no click is felt, the return spring in the head may be broken.
Works intermittently
Contact block contacts are pitted or burned. Replace the contact block — don't try to file the contacts. Check if the rated cycle count has been exceeded.
Button feels mushy or doesn't click
The spring return mechanism in the button head is worn. Replace the head. The contact block can usually be reused if it tests OK.
Quick Specs
- Bezel material
- plastic
- Component type
- control station
- Enriched by
- schneider-decoder-2026-08-12
- Lead time
- 30 Days
- Manufacturer series