Emergency Stop Switches / E-Stop Switches Non-lighted Push-lock Turn Reset
Research Notes
1. What this is
A22E-L-01 is an Omron A22E 22mm emergency stop.
2. Part-number decode
- Series: Omron A22E
- Type: emergency-stop
- Panel cutout: 22mm
3. Compatibility & ordering
Omron makes industrial command switches (A22 22mm, A16 16mm — unitized, contact in the model code), illuminated pushbuttons/pilot lights (A3, M2), and a widely-used B3 PCB tactile-switch family. Match by size, function (pushbutton/selector/indicator/E-stop), colour, illumination, and contact arrangement, then use the Omron datasheet to confirm the exact colour and voltage encoded in the part number.
4. Data-quality note
The Omron series and switch type are decoded from the part number (grounded in the omron.com catalog and DigiKey listings; A22 corroborated by curated-loop work). Omron 22/16mm command switches are unitized — the contact arrangement is part of the model code — but the exact colour and voltage suffix should be confirmed against the Omron datasheet for a precise order (not guessed here).
5. Sources
- Omron product catalog (omron.com / components.omron.com)
- Distributor listing (DigiKey / Mouser) — search the exact part number
1 source
- Omron — A22E-L-01 — omron.com
Specifications
|
Device class
|
emergency-stop
|
|
Enriched by
|
omron-decoder-2026-08-12
|
|
Lead time
|
86 Days
|
|
Manufacturer series
|
A22E
|
|
Mouser part number
|
653-A22E-L-01
|
|
Panel cutout
|
22mm
|
|
Pn status
|
decoded
|
|
Rohs status
|
RoHS Compliant
|
|
Series description
|
Omron A22E 22mm emergency-stop switch (mushroom, push-lock/turn-reset, direct-opening NC safety contact) — unitized: the contact is set by the model code
|
Installation Quick Reference
Panel cutout: 22mm. Mount with the yellow backing plate visible (required by EN/ISO 13850).
Wiring: Wire NC contacts in series with the safety relay input channels. Use dual-channel wiring for SIL 3 / PLe applications. Never wire directly to a motor contactor.
Testing: Press the e-stop and verify the machine stops within the required time. Test the reset mechanism. Repeat monthly per EN/ISO 13850.
Dimensions
Troubleshooting
E-stop won't reset (twist/pull doesn't release)
Check for debris in the mechanism. For twist-release: turn clockwise 45-90 degrees. For push-pull: pull straight out firmly. If the mechanism is stuck, the internal latch may be damaged — replace the entire head assembly.
Machine doesn't stop when e-stop is pressed
Critical safety issue. Immediately lock out the machine. Check wiring — NC contacts must be in series with the safety relay. Verify the safety relay is functioning. A broken wire in an NC circuit should cause a stop, so check for a wiring bypass.
Safety relay faults after e-stop reset
The safety relay detects a cross-fault between the two monitoring channels. Check that both NC contacts on the e-stop are switching simultaneously. One contact may be welded closed — replace the contact block.