800F-X01
Active800F 1NC Contact Block
Allen-Bradley 800F 1NC contact block.
Common Applications
Snap-on NC contact block for the entire 800F range. The $8 replacement part that fixes 90% of intermittent button problems. Wire in series for stop functions. Keep minimum 5 spares per AB panel.
Research Notes
1. Overview
The Allen-Bradley (Rockwell Automation) 800F-X01 is a 22.5 mm normally-closed (1 NC) contact block — a modular contact cartridge that snaps onto an 800F latch base mounted behind an 800F or 800FM operator. It is not a complete pushbutton: it is the back-of-panel contact element that is field-installed on a plastic latch (800F-ALP) or metal latch (800F-ALM) to add switching logic to any 800F series operator (pushbuttons, selector switches, E-stops). The 800F series is Allen-Bradley's current IEC-format 22 mm product line, replacing the older 800T series. The complementary NO contact is the 800F-X10.
Contact-block flag: YES — This is a contact block / contact cartridge only, not a complete pushbutton assembly.
2. User Sentiment
No formal review scores were found. On the r/PLC subreddit (May 2025), an engineer working with 800FP-LMT44 illuminated E-stops fitted with 800F-X01 or 800F-X01S NC contact blocks reported achieving around 300 ms of discrepancy time between contacts — relevant for safety relay tuning. The 800F-X01 is widely stocked and regarded as a commodity NC contact cartridge with a strong reliability track record; it carries a 10 million mechanical cycle rating and 4–6 mΩ contact resistance per Rockwell's own support database. The self-monitoring variant (800F-X01S) is preferred for safety circuits, while the base 800F-X01 is used for standard control logic.
3. Real-World Applications
The 800F-X01 is used across industrial automation wherever an NC switching contact is needed at a 22 mm control station. Common deployments include: E-stop pushbuttons (combined with 800F-X10 NO contacts on the latch, as in 800F-PX11 and 800F-PX02 kit assemblies), selector switches (e.g., 800FP-SM32 3-position selector needs two 800F-X10 and one 800F-X01 for OXO circuit), and motor control panel pushbutton stations. Rockwell's PowerFlex 40 configured drive installation instructions specify four 800F-X01 contact blocks for the E-stop safety circuit. The part also appears as a repair component in 194R rotary disconnect switches and 198-series relay assemblies.
4. Technical Specifications
- Type: Contact block / contact cartridge, 1 Normally Closed (NC)
- Series: Allen-Bradley 800F, 22.5 mm IEC format
- Rated insulation voltage (Ui): 690 V
- Maximum operational voltage: 600 V (screw termination; A600 / Q600)
- Thermal current (Ith): 10 A
- AC utilization category: AC-15, A600 (screw)
- DC utilization category: DC-13, Q600 (screw)
- Terminal type: Screw clamp — screw diameter 3.4 mm (0.134 in), terminal opening 7.0 mm (0.275 in); 800F-ATK2 stab terminal accessory available
- Wire range: #18–12 AWG (0.75–2.5 mm²); max (2) #14 AWG or (1) #12 AWG
- Tightening torque: 6–8 in-lb / 0.7–0.9 N-m
- Contact resistance: 4–6 mΩ
- Mechanical endurance: 1.0 × 10⁷ cycles
- Mounting: Snaps onto 800F-ALP (plastic) or 800F-ALM (metal) latch base; rotating-collar latch allows one-hand removal; front mount; bifurcated contacts; color-coded plunger
- Enclosure rating: IP65, IP66, NEMA 4, 4X, 13 (when installed on sealed operator)
- Operating temperature: −25 °C to +70 °C
- Storage temperature: −40 °C to +85 °C
- Humidity: ≤ 95 % RH (25–60 °C)
- Vibration / shock: 10 g / 100 g
- Standards: EN/IEC 60947-5-1, IEC 60947-1, UL 508
- Certifications: UL, UR, CSA, CCC, CE, UKCA
- Packaging: Standard — 10 pcs per bag (800F-NX-X01 = 1 pc per bag, same spec); bulk pack — 800F-X01-BP (100 pcs)
- Self-monitoring / safety variant: 800F-X01S (same size, adds positive-opening / self-monitoring mechanism for SIL/PLd safety circuits; B10d testing per Rockwell applies to complete device — operator + latch + contact blocks combined)
5. Ordering & Compatibility
Typical authorized-distributor pricing is approximately $15–18 USD each (OneSource ~$15.92, NorthEast Electrical ~$18.39); surplus resellers go higher (~$25–40). IMC-Direct listed $12.80 as a non-authorized price. The 800F-X01 fits both 800F plastic operators and 800FM die-cast zinc (metal) operators — up to two contact blocks can be stacked on each side of the latch (four total). Related variants: 800F-X01L (NC late-break), 800F-X01B (repair part), 800F-X01V (spring/cage-clamp termination, 300 V), 800F-X01S (self-monitoring). Kit assemblies: 800F-PX02 (latch + 2× 800F-X01), 800F-PX11 (latch + 1× 800F-X10 + 1× 800F-X01). The 800F-X01 is also listed as a contact block compatible with 194R rotary disconnects and 198-series relay assemblies.
6. Known Issues
On safety relay applications, users have noted that discrepancy monitoring windows need to be tuned — about 300 ms discrepancy between NC contacts is achievable per r/PLC field reports (May 2025). Rockwell's shallow 800F-1YP / 800F-1YM single-hole enclosures have a documented depth constraint that can prevent installation of the ALP latch + 800F-X01 front-mount contact block despite physical fit. No widespread reliability complaints were found; contact resistance is tight (4–6 mΩ) and mechanical life of 10 M cycles is well-regarded for the category.
29 sources
- 800F-X01 | Allen-Bradley | US - Rockwell Automation — rockwellautomation.com
- Cut Sheet 800F-X01 - Rockwell Automation — configurator.rockwellautomation.com
- Available Drawings for 800F-X01 - Rockwell Automation — configurator.rockwellautomation.com
- 800F-X01S | Allen-Bradley | US - Self-Monitoring Variant — rockwellautomation.com
- 800F contact block terminal screw size, opening and connector — support.rockwellautomation.com
- 800F SensEject contact blocks, latches and target tables — support.rockwellautomation.com
- Safety parameter (MTTFd, B10d) of 800F 1-Hole Enclosure E-Stop Station — support.rockwellautomation.com
- Catalog Number Explanation / Breakdown of 800F Composite Part Numbers — support.rockwellautomation.com
- Part numbers included in the 800F-PX02 Back of Components Hardware Bag — support.rockwellautomation.com
- Component breakdown of 800F-PX11 — support.rockwellautomation.com
- Resistance Reading for Bulletin 800F Contact Blocks 800F-X01 and 800F-X10 — support.rockwellautomation.com
- Ordering and Packaging of 800F-NX-X01 and 800F-X01 Contact Blocks — support.rockwellautomation.com
- Current and Voltage Switching Ratings of 800F Contact Blocks — support.rockwellautomation.com
- N.C.E.B. and N.O.E.B. auxiliary contacts for 194R rotary disconnects — 800F-X01 variant list — support.rockwellautomation.com
- Adding Contact Blocks to 800F-1YM, 800F-1YP Pushbutton Stations — support.rockwellautomation.com
- 800F Emergency Stop Operators Installation Instructions — literature.rockwellautomation.com
- PDF Catalogue No: 800F-X01 CONTACT BLOCK SCREW NO LATCH 1NC — prdsccdnstorage.blob.core.windows.net
- PDF Catalogue No: 800F-X01S CONTACT BLOCK SCREW NO LATCH 1NC SELF MONITORING — prdsccdnstorage.blob.core.windows.net
- Allen Bradley 800F Series Contact Block, 690V, 1 NC — uk.rs-online.com
- Allen-Bradley 800F-X01 :: Contact Block, 22.5mm, Plastic, 1 Normally Closed :: Rexel USA — rexelusa.com
- 800F-X01 - Routeco — routeco.com
- (A) 800F-X01 Contact Block 1NC - Klinkmann Store — store.klinkmann.com
- 800F-X01 Contact cartridge Allen Bradley - Components4Automation — components4automation.com
- Allen Bradley 800F-X01 Auxiliary Contact Block - MROSupply — mrosupply.com
- Discrepancy time with 800F-X01 NC contact blocks on E-stops : r/PLC — reddit.com
- 800F-X01 Allen Bradley | Purchase a Series A 22MM Allen Bradley Contact Block — imc-direct.com
- contact block allen-bradley 800f-x01 1nc max 600V 10a — gastroparts.com
- 議價,開關按鈕800F-X10和800F-X01 — Taobao Chinese listing combining NC/NO contact blocks — taobao.com
- 800F-X01 - Allen-Bradley (SJT Automation France) — sjtautomation.com
Specifications
|
Certifications
Third-party safety certifications. UL = required for US NEC installations. CE = EU compliance. CSA = Canadian standards.
|
UL, CSA, CE
|
|
Contact Configuration
Normally Closed — circuit is on until you press. Standard for stop/emergency functions. Wire in series with safety circuits.
|
1NC
|
|
Mechanical Life
How many press cycles before mechanical failure. Higher is better — 10M cycles at 100 presses/day = 274 years.
|
10,000,000 cycles
|
|
Terminal Type
How you connect wires. Screw clamp is most common in industrial. Spring cage is faster but requires proper ferrules.
|
Screw clamp
|
Installation Quick Reference
Mounting: Snap onto the rear of any compatible button body in the same series. The latch clicks audibly when properly seated. Some models require a mounting adapter.
Wiring: Terminals are marked NO (11/12) or NC (21/22). Use 0.5-2.5mm² wire with ferrules. Tighten to 0.8 Nm. Verify with a multimeter before energizing.
Dimensions
Wiring Diagram
Troubleshooting
Intermittent switching
Silver contacts are pitted from arcing. Replace the contact block — they are consumable parts. If arcing is severe, check that the switched load doesn't exceed the contact rating (typically 6A at 120VAC).
Contact block won't snap onto button body
Verify the contact block series matches the button head series (e.g., Schneider ZB4 blocks fit ZB4 heads only, not ZB5). Check for debris or damage on the mounting tabs.
Where to Buy
Price range
$22.8 — $24.04
across 2 distributors
Quick Specs
- Certifications
- UL, CSA, CE
- Contact Configuration
- 1NC
- Mechanical Life
- 10,000,000 cycles
- Terminal Type
- Screw clamp
What People Are Saying
“Snap-on NC contact block for the entire 800F range. The $8 replacement part that fixes 90% of intermittent button problems. Wire in series for stop functions. Keep minimum 5 spares per AB panel.”